服务热线
13210558111
1. smoke extraction system installed in the pipeline, usually in a closed state, when the fire manual or electric open up smoke. When close the exhaust pipe, the flue gas temperature reached 280 degrees, in a certain period of time to meet the fire stability and fire integrity requirements, since the exhaust effect of the valve.
2.常闭型排烟防火阀(常闭,电讯号开启,280度熔断关闭,或手动关闭)一般应用于排烟系统中,可在排烟风机吸入口安装一个,火灾时由消控室控制开启,关闭时也可连锁关闭该排烟风机.
2. normally closed type smoke damper (normally closed, open telecommunications number, 280 degrees blown off, or manually shut down) is generally used in the exhaust system, the suction exhaust fan installed a fire control room control by the consumer to open, closed when the chain to close the exhaust fan.
3.排烟阀,各个单位叫法不同,有的根据它的动作温度叫做排烟阀,有的根据它的用途性质叫做防火阀,但是对于设备方只是把普通防火阀的熔断金属换成280度熔断的那一种.
3. exhaust valve, the various units of different names, some called according to its operating temperature of exhaust valve, depending on the nature of its use is called the fire valve, but only for the equipment side of the ordinary damper fuse metal into the a 280 fuse.
施工安装
Construction installation
彩神VII 1. 防火阀可与通风机、排烟风机联锁.
1. fire dampers can be interlocked with ventilators and smoke exhaust fans
2. 阀门的操作机构一侧应有不小于200mm 的净空间以利检修.
2., the valve side of the operating mechanism should be no less than 200mm of the net space in order to facilitate the overhaul
3. 安装阀门前必须检查阀门的操作机构是否完好,动作是否灵活有效.
3., before installing the valve, you must check the valve operating mechanism is intact, the action is flexible and effective
4. 防火阀应安装在紧靠墙或楼板的风管管段中,防火分区隔墙两侧的防火阀距墙表面不应大于200mm,防火阀两侧各2.0m范围内的管道及其绝热材料应采用不燃材料.
4. fire safety valve should be installed in the pipe against the wall or floor wind section, fire valve fire partition walls on both sides of the distance from the wall surface should be no more than 200mm, the pipeline fire valve on both sides of the 2.0m range and the insulation material used should be made of non combustible materials.
5. 防火阀应单独设支吊架,以防止发生火灾时管道变形影响其性能.
彩神VII 5. fire dampers shall be provided with separate hangers to prevent pipe deformation during fire and affect its performance
6. 防火阀的熔断片应装在朝向火灾危险性较大的一侧.
6. the fuse shall be mounted on the side of the fire that is dangerous